Easy to use power kit for common WiFi
thermostats
Universal Fit – Works with Carlin, Beckett
and Honeywell primary controls
Replaces Beckett 51950U Ready Kit or
51970U Terminal base
Replaces Honeywell R8184M when
installed with Carlin primary control
Heavy Duty 16 Amp Relay for added
durability
• Designed for quick installation
Warning
1. The 98435S kit must be installed only by a quali-
ed service technician.
2. Always disconnect power source before wiring to
avoid electrical shock or damage to the control.
All wiring must comply with applicable codes and
ordinances.
3. Thermostat terminals (T-T) provide a current
source. Never apply external power to these
terminals under any circumstances.
Mounting
Mount the interface board on the burner 4x4 junc-
tion box as shown in Figure 1. Insert the trans-
former hub through a junction box knockout and
secure with lock nut.
The control location must not exceed the ambi-
ent temperature limit, listed in the primary control
data sheet.
Operation
1. Fan and cooling check – Set thermostat to call
for cooling or fan. Verify correct operation.
2. Heating control check – Set thermostat to call
for heat. Follow the primary control data sheet
checkout procedure to verify.
3. If control does not operate correctly, check all
wiring and wiring connections.
Transformer input (primary)
120 VAC, 60 HZ
Transformer output (secondary)
24 VAC, 60 HZ, 40 VA
Control specifications
Refer to primary control
data sheet
Max ambient temp
140°F
Kool Kit
24 VAC power adapter kit for adding
WiFi thermostats with AC interface to
Oil Boilers and Furnaces
Model 98435S
Includes circuit board, quick connect
wire harness, 24 VAC transformer
Model 98435S1
Includes replacement circuit board only,
24 VAC transformer not included
Installing & Wiring
Carlin Combustion Technology, Inc.
126 Bailey Road • North Haven, CT 06473 • 203-680-9401 • Fax 203-680-9403
Tech Support 800-989-2275 • carlincombustion.com
Figure 1
The following are common
thermostat terminal designations.
Refer to your thermostat
installation/wiring instructions for
the proper terminal designations.
C = 24 VAC common
R = 24 VAC hot
W = Heat
Y = Cool
G = Fan
The following are common thermostat terminal
designations. Refer to your thermostat installation/wiring
instructions for the proper terminal designations.
C = 24 VAC common
R = 24 VAC hot
W = Heat
Y = Cool
G = Fan
Thermostat wired into the
burner primary control
WARNING: Wiring must comply with local and national
electrical codes.
1. Remove the factory installed jumper from the T-T terminals of the burner
primary control.
2. Connect the red and white wires from the Kool Kit board to the T-T
terminals on the burner primary control. The wires are not polarity
sensitive.
3. Connect the thermostat terminals to the Kool Kit interface board as
shown.
Note: Thermostat designations may vary depending on the thermostat
brand. Refer to the thermostat wiring instructions for the proper terminal
designations.
4. (Optional) Connect the cooling contactor and the fan relay to the Kool Kit
interface board as shown.
Thermostat wired into the
HydroStat 3250-Plus
WARNING: Wiring must comply with local
and national electrical codes.
1. Verify the factory installed jumper is
installed on the T-T terminals of the burner
primary control.
2. Connect the red and white wires from the
Kool Kit board to the T-T terminals on the
HydroStat 3250-Plus. The wires are not
polarity sensitive.
3. Connect the thermostat terminals to the
Kool Kit interface board as shown.
Note: Thermostat designations may vary
depending on the thermostat brand. Refer
to the thermostat wiring instructions for the
proper terminal designations.
4. (optional) Connect the cooling contactor
and the fan relay to the Kool Kit interface
board as shown.
AcuTemp Indirect Tank Control wired into the HydroStat 3250-Plus
WARNING: Wiring must comply with local and national electrical codes.
1. Verify the factory installed jumper is installed on the T-T terminals of the burner primary control.
2. Connect the output contacts from the AcuTemp to the R and W terminals on the Kool Kit interface board. The terminals are not
polarity sensitive.
3. Connect the 24 VAC input AC1 on the AcuTemp to the C terminal on the Kool Kit interface board. Connect the 24 VAC input AC2 on
the AcuTemp to the R terminal on the Kool Kit interface board.
4. Connect the red wire from the Kool Kit board to the L1 Terminal on the Hydrostat 3250-Plus. Be sure to comply with local and
national electric codes as this is a 120 VAC connection
5. Connect the white wire from the Kool Kit board to the ZR terminal on the Hydrostat 3250-Plus. Be sure to comply with local and
national electric codes as this is a 120 VAC connection.
6. Connect the domestic hot water circulator to the L2 (neutral) and ZR (hot) terminals on the Hydrostat 3250-Plus.
7. Set the Z/I switch on the Hydrostat 3250 to the I position. If the switch is left in the Z position the boiler may not provide adequate
hot water.
© Copyright 2019 Carlin Combustion Technology, Inc.
MN98435 082119