9/24/2018
6
Time Overcurrent Relays
U
I
ECE525
Lecture 11
Example continued
The desired coordination can be accomplished by:
increasing the time dial settings as one proceeds toward
the source.
» If relay R2 is expected to provide backup protection for
relay R4,
» Then R4, the relay with the greatest source impedance, would
be set with the lowest time dial setting
Time Overcurrent Relays
U
I
ECE525
Lecture 11
Example continued
» If I
MIN
is defined as the minimum fault current,
» Then the pickup current must be set at or below this current but
above maximum load current.
» Usually with a margin around both
» For relays R2 and R3, the TDS must be set to trip no
faster then the next downstream device when the fault
current is maximum for an out of zone fault