THE CITY OF NEW YORK
DEPARTMENT OF ENVIRONMENTAL PROTECTION
Bureau of Environmental Compliance
59-17 Junction Boulevard, 9
th
Floor, Flushing, New York 11373
Records Control (718) 595–3855
Equipment nomenclature explanation ( Boiler, Burner and Controls)
Type of performance testing conducted (UL, HI, NRTL, etc.) please specify
Supplementary explanation if needed
Manufacturer datasheets must be attached with all non-accepted equipment
Professional Engineer Certification
I attest under the penalties of perjury:
1. I have personally examined and am familiar with the information contained in this submittal, including any and
all documents accompanying this certification statement.
2. That, based on my inquiry of those individuals responsible for obtaining the information, the information
contained in this submittal is, to the best of my knowledge, true, accurate and complete.
3. That, a licensed stationary engineer will be in attendance at the facility at all times.
4. I have personally reviewed the manufacturer’s test data and certify that the equipment will meet the following
operating conditions in the field:
a. A smoke reading of #3 or less on the Bacharach Scale
b. Stack losses will not exceed 17% for oil and 20% for natural gas
c. Overall efficiency will be at least 78%
5. That, at the time of owner equipment acceptance, overall efficiency tests according to the methods and
procedures outlined by ASME will be conducted and properly certified by a professional engineer registered in
the State of New York.
6. That, written notification will be made to the Department at least 15 days prior to any such tests so that
representatives of the Department may witness said tests.
7. That, combustion controls for the installation will be fully automatic with the air/fuel ratio being controlled by
feedback based upon continuous analysis of the flue gases at the boiler outlet and that this analysis will enable
the combustion controller to continuously maintain the operating conditions for overall efficiency, stack loss
and smoke readings as indicated above.