45J/K/Q-P-1312
PRODUCT INFORMATION IS SUBJECT TO CHANGE WITHOUT NOTICE.
MULTI FUNCTION, RA-NC
PNEUMATIC CONTROL
SEQUENCE 1312
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
PRIMA RY FLOW
ELECTRIC HEA T
HW HEAT
INDUCED FLOW
0
20
40
60
80
100
% CAPACITY
T-STAT PRESSURE
CONSTANT VOLUME FAN POWERED
TERMINAL UNIT PNEUMATIC CONTROL
SEQUENCE 1312
RANC, Multi-Function Control of VAV With Optional
Reheat, and Constant Volume Fan Operation
1312 — User defined primary air flow setpoints are main-
tained regardless of central system pressure, while terminal
fan runs continuously. Primary air flow is controlled by a multi-
function reset volume controller. If necessary, the user can
opt to field adjust reset start, reset span, select N.O. or N.C.
damper by turning a dial, and choice of using Direct or
Reverse acting thermostats.The controller is factory set
to provide the following sequence of operation:
Under load for cooling, primary air flow is at maximum when
the thermostat (Reverse Acting), is at or below 3 psig.Primary
air flow should not exceed fan air flow setpoint.When thermo-
stat branch pressure increases, primary air flow reduces to
the user defined minimum air flow setpoint at 8 psig. As primary
air flow is reduced, the constant volume terminal fan propor-
tionally induces ceiling plenum return air or ducted return air,
to maintain a constant volume of air to the occupied space.
Under a load for heating, thermostat branch pressure will
continue to increase.Optional, proportional hot water heat
(8-13 psig),or sequenced on/off staged electric heat (up to
3-stages), will be initiated in response to the thermostat signal.
Pneumatic air consumption of the multi-function controller
is 28.8 scim at 20 psig (.472 l/m @ 138 kPa). Upon a loss
of Subject pneumatic air, the terminal damper fails closed
(Normally Closed).