F92 Series Air Volume Controls for Shallow Wells Product/Technical Bulletin
2
Installation
The F92 Series Air Volume Control for Shallow Wells
connects to the air charging section of the pump. Install
the control in the tank as follows:
1. If you are using Teflon® thread sealing tape, wrap
the 1-1/4 in. NPT threads on the control. Overlap
the tape half its width to make two layers, and
continue to where the thread ends at the large end.
If you are using pipe sealant instead of Teflon tape,
apply a generous amount of sealant to the male
threads.
2. Use a wrench on the flat sides of the control body
to screw the control into a tank opening located
about 2/3 of the way up.
Note: The tank must have a diameter of at least
229 mm (9 in.) to allow room for the float to operate.
3. The F92B Control has a 1/4 in. tapped opening for
a pressure port at the top of the control. (The
F92A Control does not have a tapped opening.)
When you install a gage into this pressure port,
wrap two turns of Teflon thread sealing tape around
the male threads of the gage. Overlap the tape half
its width to make two layers. If you are using pipe
sealant instead of Teflon tape, apply a generous
amount of sealant to the male threads.
If you do not install a gage, install a standard
1/4 in. pipe plug in the opening. Wrap two turns of
Teflon thread sealing tape around the male threads
of the plug or gage. Overlap the tape half its width
to make two layers. If you are using pipe sealant
instead of Teflon tape, apply a generous amount of
sealant to the male threads.
Note: Do not overtighten. 6.8 N•m (5 lb·ft) of torque is
adequate to seal the threads.
4. When the F92 Control is installed, run 5 mm
(3/16 in.) tubing from the snifter valve on the pump
to the air valve on the control.
IMPORTANT: Use only Teflon® thread sealing tape
or pipe sealant that is compatible with plastic. Pipe
sealant meant for use with metal may corrode the
plastic body, causing it to crack.
IMPORTANT: Tighten (not overly tight) with the air
valve and assembly pointed down. Ensure that the
wrench does not slip and damage the air valve
casing assembly.
Figure 2: F92 Series Air Volume Control for Shallow Wells Dimensions, mm (in.)
IMPORTANT: Do not use the gage opening to
connect the pressure switch controlling the
operating pump. It must only be used for a pressure
gage because the opening can become plugged.