Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
Supersedes Publication 1756-PM016R-EN-P - November 2022
Programming Manual
Original Instructions
Logix 5000 Controllers
Security
1756 ControlLogix, 1756 GuardLogix, 1769 CompactLogix,
1769 Compact GuardLogix, 1789 SoftLogix, 5069
CompactLogix, 5069 Compact GuardLogix, Studio 5000
Logix Emulate
Logix 5000 Controllers Security
2 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize
themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to
be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING:
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to
personal injury or death, property damage, or economic loss.
ATTENTION:
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss.
Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD:
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous
temperatures.
ARC FLASH HAZARD:
Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will
cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for
Personal Protective Equipment (PPE).
Rockwell Automation recognizes that some of the terms that are currently used in our industry and in this publication are not in
alignment with the movement toward inclusive language in technology. We are proactively collaborating with industry peers to
find alternatives to such terms and making changes to our products and content. Please excuse the use of such terms in our
content while we implement these changes.
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 3
Summary of changes
This manual includes new and updated information. Use these reference
tables to locate changed information.
Grammatical and editorial style changes are not included in this summary.
Global changes
None in this release.
New or enhanced features
This table identifies changes related to new or enhanced features in this
release.
Change
Added a note that states that locked and protected project
content can be deleted without a password, license, or
dongle.
Source Protection
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 5
Table of Contents
Studio 5000 environment ........................................................................... 7
Additional resources .................................................................................... 8
Legal notices ................................................................................................. 8
Chapter 1
Introduction ................................................................................................ 11
FactoryTalk Security ................................................................................... 11
Permission sets and Logical Names ................................................... 11
Source Protection ....................................................................................... 12
Chapter 2
Introduction ................................................................................................15
Considerations and limitations for License protection and locked
components .......................................................................................... 16
Enable source protection........................................................................... 18
Disable the Configure Source Protection menu option .......................... 18
Protect components with Source Keys ..................................................... 19
About source keys ................................................................................ 20
Source key names ................................................................................ 20
Source key file ....................................................................................... 21
Apply Source Key protection to a component ................................... 22
Specify a Source Key file and location ......................................... 24
View components without a key .................................................. 26
Verify source key protection on a component .............................27
Remove access to a protected routine ..........................................27
License Source Protection for components .............................................27
Protect components with Licenses .................................................... 28
Add Execution Protection to License-protected components ......... 30
Apply License Protection to one or more components ..................... 31
Lock a component ................................................................................ 33
Lock all License-Protected content ..................................................... 34
Add an LV instruction to monitor license status ............................... 34
Share License privileges with other users on your network ............. 34
Provide License privileges to other users ..................................... 35
Provide license privileges for remote desktop users ................... 39
Securing a ControlLogix controller with the Logix CPU Security Tool..44
Accessing a secured controller ................................................................. 48
Removing security from a controller with the CPU Security Tool ......... 51
Removing a password ................................................................................ 53
Summary of changes
Preface
Security overview
Configuring source protection
in the Logix Designer
application
Table of Contents
6 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
Appendix A
Product policies and securable actions .................................................... 56
Product policies and securable
actions supported by
FactoryTalk Security
Index
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 7
Preface
This manual explains how to configure security for the Logix Designer
application. It also explains how to set up source protection for your logic and
projects. This manual is one of a set of related manuals that show common
procedures for programming and operating Logix 5000 controllers.
For a complete list of common procedures manuals, refer to the Logix 5000
Controllers Common Procedures Programming Manual, publication
1756-PM001.
The term Logix 5000 controller refers to any controller based on the Logix
5000 operating system.
Rockwell Automation recognizes that some of the terms that are currently
used in our industry and in this publication are not in alignment with the
movement toward inclusive language in technology. We are proactively
collaborating with industry peers to find alternatives to such terms and
making changes to our products and content. Please excuse the use of such
terms in our content while we implement these changes.
The Studio 5000 Automation Engineering & Design Environment® combines
engineering and design elements into a common environment. The first
element is the Studio 5000 Logix Designer® application. The Logix Designer
application is the rebranding of RSLogix 5000® software and will continue to
be the product to program Logix 5000controllers for discrete, process,
batch, motion, safety, and drive-based solutions.
The Studio 5000® environment is the foundation for the future of
Rockwell Automation® engineering design tools and capabilities. The Studio
5000 environment is the one place for design engineers to develop all
elements of their control system.
Studio 5000 environment
Preface
8 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
These documents contain additional information concerning related
products from Rockwell Automation.
Resource
Description
Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1
Provides general guidelines for installing a
Rockwell Automation industrial system.
FactoryTalk Security System Configuration Guide,
publication FTSEC-QS001
Provides additional information on FactoryTalk
security.
Product Certifications website,
http://ab.rockwellautomation.com
Provides declarations of conformity, certificates,
and other certification details.
You can view or download publications at
http://www.rockwellautomation.com/literature/. To order paper copies of
technical documentation, contact your local Allen-Bradleydistributor or
Rockwell Automationsales representative.
Rockwell Automation publishes legal notices, such as privacy policies, license
agreements, trademark disclosures, and other terms and conditions on the
Legal Notices page of the Rockwell Automation website.
End User License Agreement (EULA)
You can view the Rockwell Automation End User License Agreement (EULA)
by opening the license.rtf file in your product's install folder on your hard
drive.
The default location of this file is:
C:\Program Files (x86)\Common Files\Rockwell\license.rtf.
Open Source Software Licenses
The software included in this product contains copyrighted software that is
licensed under one or more open source licenses.
You can view a full list of all open source software used in this product and
their corresponding licenses by opening the oss_licenses.txt file in your
product's OPENSOURCE folder on your hard disk drive. This file is divided
into these sections:
Components
Includes the name of the open source component, its version number,
and the type of license.
Copyright Text
Includes the name of the open source component, its version number,
and the copyright declaration.
Additional resources
Legal notices
Preface
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 9
Licenses
Includes the name of the license, the list of open source components
citing the license, and the terms of the license.
The default location of this file is:
C:\Program Files (x86)\Common Files\Rockwell\Help\ControlFLASH
Plus\Release Notes\OPENSOURCE\oss_licenses.txt.
You may obtain Corresponding Source code for open source packages
included in this product from their respective project websites. Alternatively,
you may obtain the complete Corresponding Source code by contacting
Rockwell Automation via the Contact form on the Rockwell Automation
website:
https://www.rockwellautomation.com/global/about-us/contact/contact.page.
Include "Open Source" as part of the request text.
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 11
Chapter 1
Security overview
This chapter provides an overview of the security features available in the
Logix Designer application.
The following features are the main security features that protect controller
projects:
FactoryTalk® Security software, which provides permission-based
control.
Source Protection, which protects the logic in controller projects.
FactoryTalk® Security integrates a common security model across all
FactoryTalk enabled products. FactoryTal Services Platform (FTSP)
includes the FactoryTalk Administration Console that provides the interface
for configuring your system. FactoryTalk Services Platform (FTSP) software is
installed during the installation of the Logix Designer application.
Use FactoryTalk Security to control access to the logic in your projects with
centrally managed, role-based policy enforcement.
For more information about FactoryTalk Security, see the FactoryTalk
Security System Configuration Guide, publication FTSEC-QS001.
Permission sets and Logical Names identify a set of actions that are allowed
or denied for one or more user groups or computer groups. You use
permission sets and Logical Names to define user permissions in the
FactoryTalk Administration Console. Use permission sets to apply the same
permissions to multiple controllers or project components. Use a Logical
Name to associate permissions with a specific controller. When you use a
Logical Name, it must match the name of the controller.
When a user opens a project that has been secured with a permission set or a
Logical Name and configured to use only the selected security authority, the
Logix Designer application checks the ID of the FactoryTalk Directory to see if
it matches the ID stored in the project.
If the ID matches, the Logix Designer application checks the directory
and finds the Logical Name (that matches the controller name), or the
permission set associated with the project, and gets the permissions
for the current user/computer combination.
If the ID does not match, the project uses the Guest User permissions
defined for that permission set or Logical Name.
Introduction
FactoryTalk Security
Permission sets and Logical
Names
Chapter 1 Security overview
12 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
When a user opens a project that has been secured but has not been
configured to use only the selected security authority, the Logix Designer
application checks the connected FactoryTalk Directory, finds the Logical
Name or the permission set associated with the project, and gets the
permissions for the current user/computer combination. Rockwell
recommends configuring the project to use only the selected security
authority to maintain control over the directory that secures the project.
Permissions for Guest Users
When you configure permission sets and logical names in the FactoryTalk
Administration Console, you can also configure permissions for Guest Users.
The permissions for Guest Users determine the level of access for users who
are not authenticated on the same FactoryTalk directory that the project was
secured with.
Permissions for Guest Users are cached in the project file to which they are
associated. However, the permissions are only stored in the project file for
permission sets that have been applied to objects by a user of the primary
FactoryTalk directory.
Refer to the FactoryTalk online help for more information on permissions for
Guest Users.
Source Protection limits users' ability to view and edit routines and Add-On
Instructions, including equipment phase state routines, without the
associated source key or license. Apply Source Key Protection or License
Source Protection to routines and Add-On Instructions. Apply Execution
Protection to license-protected components to allow execution only on
controllers with a specific execution license.
When protecting a component with License Source Protection, optionally lock
the component. A locked component does not require the source license to
open the project or execute the locked component, allowing more secure
distribution. A user with the correct license must unlock a component to allow
viewing or editing. Rockwell recommends locking unlocked components in
projects that are distributed from trusted development environments to
unsecured environments to safeguard your intellectual property.
Tip: Routines and Add-On Instructions are currently the only project component types that support
Source Protection.
Tip: Execution Protection and component locking is supported only on Compact GuardLogix 5380,
CompactLogix 5380, CompactLogix 5480, ControlLogix 5580, and GuardLogix 5580 controllers in
versions 30 and 31 of the Logix Designer application.
License Source Protection and Execution Protection Licenses require the use
of CmSticks and CmCards:
Source Protection
Chapter 1 Security overview
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 13
On the computer running the Logix Designer application, a CmStick,
CmCard, or other compatible Wibu device that contains licenses
required for opening a license-protected project and working with
project components.
Tip: On CompactLogix 5380, CompactLogix 5480, ControlLogix 5580, Compact GuardLogix
5380, and GuardLogix 5580 controllers, a CmStick, CmCard, or other compatible Wibu device
is not required to open a project containing locked components.
On the controller, a CmCard that contains execution licenses required
to run a project that contains components protected with Execution
Protection. If a required execution license is missing, the project does
not download to the controller. If the project has already been
downloaded and the license expires or the CmCard is removed, a
major fault occurs when the controller is switched to Run mode.
Tip: You can delete protected or locked content in a project. You do not need a password,
dongle, or license to delete protected content.
The following table describes the types of Source Protection available.
Protection option
Supported controllers
Description
Source Key (Password-based)
Source Protection
All Logix 5000 controllers Simple legacy protection, not recommended for hardened
intellectual property protection.
Component source code (logic) is protected with a
password.
Password must be available to view or edit protected
components.
Optionally, can be configured to allow logic to be viewed
when password is not available.
License Source Protection CompactLogix 5370, ControlLogix
5570, Compact GuardLogix 5370,
and GuardLogix 5570 controllers
Hardened intellectual property protection for sensitive
content:
Component source code (logic) is protected with a
License on a CmStick installed on the computer running
the Logix Designer application.
License must be present to open or import the file
containing the protected components.
Licenses can be configured with different access levels
to allow viewing or editing protected components..
License Source Protection
(Locked)
CompactLogix 5380, CompactLogix
5480, ControlLogix 5580, Compact
GuardLogix 5380, and GuardLogix
5580 controllers
Provides hardened intellectual property protection for
sensitive content and allows easy transfer of projects:
Component source code (logic) is protected with a
license on a CmStick installed on the computer running
the Logix Designer application.
Executable code is protected and stored separately from
the source code.
Chapter 1 Security overview
14 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
Protection option
Supported controllers
Description
License Source Protection
(Unlocked)
CompactLogix 5380, CompactLogix
5480, ControlLogix 5580, Compact
GuardLogix 5380, and GuardLogix
5580 controllers
Provides protection and access control based on
permissions in the license:
Users without a dongle can work with unprotected parts
of the project, but users cannot view or edit the
protected content. The dongle is required to work with
the protected content.
To lock or unlock a component, the source license must
be present on a CmStick plugged into the computer
running the Logix Designer application, and the license
must contain the View permission.
License Source Protection +
License Execution Protection
CompactLogix 5380, CompactLogix
5480, ControlLogix 5580, Compact
GuardLogix 5380, and GuardLogix
5580 controllers
Limits execution of valuable content to only authorized
controllers:
Provides same protection as License-based Source
Protection.
Additionally, components can be protected with an
Execution License.
Protected components can only be downloaded and
executed on a controller that contains a CmCard with the
correct execution license.
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 15
Chapter 2
Configuring source protection in the Logix
Designer application
This chapter describes how to enable and apply source protection for your
Logix Designer components, such as routines and Add-On Instructions. You
can protect project components using Source Key protection or License
protection. You can also apply Execution Protection to source-protected
components to allow execution only on controllers with a specific execution
license.
Source Key protection:
Protects components using existing source keys.
Tip: You can optionally allow source-protected components to be available in a read-only
format on a system that does not have the source key required for access.
License protection:
Protects components with specific licenses.
Tip: License Source Protection is not supported on Sequential Function Chart routines in
versions 30 and later of the Logix Designer application.
Execution Protection is an extension of License-Based Source
Protection. You can apply Execution Protection to limit the execution
of routines and Add-On Instructions, including equipment phase state
routines, to controllers that contain a specific execution license.
When you protect a component with License Source Protection, you
can also lock it. When you lock a component, the routine's logic is
compiled into executable code and encrypted. It is only decrypted by
the controller when it is ready to be executed. As a result, project files
containing locked components can be shared with users without
licenses to work with the locked components. Those users can work
with unprotected parts of the project, upload and download the project
file, and even copy and paste locked components into other project
files. Rockwell recommends locking unlocked components in projects
that are distributed from trusted development environments to
unsecured environments in order to safeguard your intellectual
property.
Tip: Execution Protection and component locking is supported only on Compact GuardLogix
5380, CompactLogix 5380, CompactLogix 5480, ControlLogix 5580, and GuardLogix 5580
controllers in version 30 of the Logix Designer application.
Introduction
Chapter 2 Configuring source protection in the Logix Designer application
16 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
Keep the following considerations and limitations in mind when using
License Source Protection with routines and Add-On Instructions for
CompactLogix 5380, CompactLogix 5480, ControlLogix 5580, Compact
GuardLogix 5380, and GuardLogix 5580 controllers.
Sequential Function Chart routines cannot be protected with License
Source Protection and execution protection.
Function Block Diagram routines cannot be protected with License
Source Protection and execution protection.
You cannot overwrite a locked routine with a locked routine of a
different language. If a locked routine needs to be replaced with a
locked routine of a different language, first unlock the routine in the
target file.
You cannot overwrite a locked routine with an unlocked routine, and
vice versa. To replace a locked routine with an unlocked routine, and
vice versa, first delete the routine to be replaced.
If you overwrite a locked ladder logic routine that contains label (LBL)
instructions with a locked ladder logic routine that contains similar
labels, other workstations can lose correlation with the project. To
recover correlation, upload the project on the affected workstations.
The controller SD card holds a maximum of 63 active or expired
licenses, plus the Rockwell activation license for Execution Protection.
If the SD card contains more than 64 licenses, downloads with
license-protected content fail to the controller. To remove unwanted
licenses, use the removal option on the Wibu administration portal.
When you lock an Add-On Instruction, the data included in tags is
protected but not to the extent that the logic is protected. If your tags
contain sensitive data, Rockwell recommends putting that data in
literals rather than in tags. Literals are protected at the same level as
the logic in locked routines and Add-On Instructions. In
programmable logic, a literal is a value that is expressed as itself rather
than as a variable's value or the result of an expression.
Limitations for locked components
After a routine or an Add-On Instruction (AOI) is locked, strict limits apply to
changes made to the routine or to other components the routine references.
This table lists limitations that apply to locked components. An authorized
user can run a locked component. To view or edit a component an authorized
user must unlock the component.
Limitation
Affects routines
Affects AOIs
Cannot resize an array that is referenced by a locked routine.
x
Cannot change the target of an alias that is referenced by a locked routine.
x
Considerations and
limitations for License
protection and locked
components
Chapter 2 Configuring source protection in the Logix Designer application
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 17
Limitation
Affects routines
Affects AOIs
Cannot change a BOOL alias that targets the bit of an integer to target a
different bit. However, changing the alias to target a different integer is
allowed.
x
Cannot change the target of an alias that is referenced by a locked routine
to a tag of a different type.
x
Cannot change the target of an alias of a member of a UDT or array element
to a target at a different offset from the beginning of the tag.
x
Cannot change an alias referenced by a locked routine to a base tag.
x
Cannot change a base tag that is referenced by a locked routine to an alias.
x
Cannot change an InOut program parameter that is referenced by a locked
routine to anything other than an InOut program parameter.
x
Cannot change a Produced tag to anything other than a Produced,
Consumed, Module Input tag or Module Output tag when the Produced tag
is:
Referenced by a locked routine, and
Used in a COP, CPS, MAOC or as an InOut argument to an AOI in that
locked routine.
x
Cannot change a Produced tag that is used in an IOT instruction to anything
other than a Produced or Module Output tag.
x
Cannot change a Consumed tag to anything other than a Produced,
Consumed, Module Input tag, or Module Output tag when the Consumed tag
is:
Referenced by a locked routine, and
Used in a COP, CPS, MAOC or as an InOut argument to an AOI in that
locked routine.
x
Cannot change a Module Input tag to anything other than a Produced,
Consumed, Module Input tag, or Module Output tag when the Module Input
tag is:
Referenced by a locked routine, and
Used in a COP, CPS, MAOC or as an InOut argument to an AOI in that
locked routine.
x
Cannot change a Module Output tag to anything other than a Produced,
Consumed, Module Input tag, or Module Output tag when the Module Output
tag is:
Referenced by a locked routine, and
Used in a COP, CPS, MAOC or as an InOut argument to an AOI in that
locked routine.
x
Cannot change a Module Output tag that is used in an IOT instruction to
anything other than a Produced or Module Output tag.
x
Cannot change a standard tag referenced by a locked routine to a
Produced, Consumed, Module Input, or Module Output tag, if that tag is used
by a COP, CPS, MAOC or used as an AOI InOut argument in that locked
routine.
x
Cannot re-order the members of a User Defined Type of a tag that is
referenced by a locked routine or AOI.
x
x
Cannot change the data type of a tag that is referenced by a locked routine.
x
Cannot update a profile in a way that changes the data type of a Module
Defined Tag that is referenced by a locked routine.
x
x
Cannot add, remove, or change the data type of a member of a User
Defined Data Type of a tag that is referenced by a locked routine or AOI.
x
x
Chapter 2 Configuring source protection in the Logix Designer application
18 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
Limitation
Affects routines
Affects AOIs
Cannot reorder, add, change the data type of, or remove parameters in an
AOI referenced by a locked routine or AOI.
x
x
Cannot convert a project containing locked routines or AOIs to a different
controller family.
x
x
Cannot move locked routines or AOIs to a project of a different controller
family.
x x
Cannot change the target of an AOI output parameter that aliases a local
tag if the AOI is used in a locked AOI.
x
Cannot change the targets of two aliases referenced by a locked routine
currently targeting different base tags to the same base tag.
x
Cannot change the targets of two aliases referenced by a locked routine
currently targeting the same base tag to target different base tags.
x
Cannot change the type of a base tag targeted by an alias that is
referenced by a locked routine.
x
Cannot change an external Output that is referenced by a locked routine to
a non-Output.
x
Cannot change an external Output that is referenced by a locked routine to
a local Output.
x
Cannot change a local tag that is referenced by a locked routine to an
external Output.
x
If Source Protection is unavailable and is not listed in the Tools > Security
menu, enable the Source Protection feature by running the RS5KSrcPtc.exe
tool on the installation CD. The menu item is also enabled when a CmStick
containing a license with protect permissions is inserted into any USB port on
the computer.
Follow these steps to enable Logix Designer source protection.
1. Open the ENU\Tools\Source Protection Tool\Vxx.xx folder on the
Logix Designer installation CD.
2. Run the RS5KSrcPtc.exe file.
You can disable the ability to configure source protection on a workstation by
removing the Configure Source Protection option from the Tools > Security
menu.
IMPORTANT
Write down the source keys or make a copy of the sk.dat file and store in a secure
location before deleting the sk.dat file.
1. Open the protected project in the Logix Designer application.
2. Select Tools > Security > Configure Source Protection.
3. In the Source Protection Configuration dialog box, select Source Key
Configuration.
4. In the Source Key Configuration dialog box, select Disable Ability To
Configure.
5. In the dialog box that prompts you to confirm the action, select Yes.
Enable source protection
Disable the Configure
Source Protection menu
option
Chapter 2 Configuring source protection in the Logix Designer application
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 19
6. In the dialog box that asks if you want to delete the source key file
(sk.dat), select Yes to remove the source key file from the computer, or
select No to keep the source key file.
Configure Source Protection is removed from the Tools > Security
menu.
Tip: The menu item will not disappear if a CmStick containing a license with the
Protect
permission is connected to the computer.
When Source Key protection is applied to a component, that component is
source-protected. Source keys are user-generated, case-sensitive passwords
that lock Logix Designer components from being viewed or modified by third
parties.
IMPORTANT
Source Protection can be applied only on a project file that is offline.
Tip: For Add-on Instructions, Source Protection settings cannot be modified if the Add-On Instruction
is sealed. If you wish to source protect and seal an Add-On Instruction, you must apply the source
protection settings before sealing.
Tip: Password source protection is designed to work with a relatively small number of source keys in
the sk.dat file. When the number of source keys becomes large, there is a corresponding
performance impact when opening source protected projects in the Logix Designer application or
opening the Source Protection dialog box.
When a component is protected with a Source Key, users without the source
key cannot alter the logic of the component. This affects the following
features:
Editing - The Language editor does not open, and the edit menus in
the Controller and Logical Organizers are unavailable. The component
icon is also unavailable. If the component is protected with the
Viewable option, users can open the routine editor in read-only mode.
Printing - Routines cannot be printed. Add-On instruction can be
printed, but the routines and local tags are not included in the print
out. Routine logic and Add-On Instruction local tags can be printed if
components are protected with the Viewable option.
Exporting - The protected component is written to the export file in an
encoded format.
Component Properties - All controls on the dialog boxes of the
components are read-only.
Search and Replace - Find All is the only available search type source.
Find Next, Replace All, and Replace Next skip the protected
component. When the protected component is skipped, a message
appears on the status bar indicating the source is not available. This
message is also logged to the Search Results tab when performing a
Replace All search. If a component is protected with the Viewable
option, search is permitted but replace is still prevented.
Because users cannot view the logic of a protected routine, the Find All search
results items do not navigate to the found locations. This affects the following:
Protect components with
Source Keys
Chapter 2 Configuring source protection in the Logix Designer application
20 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
Navigation - Users cannot navigate to a protected component.
Verification - Users cannot navigate to an error in a protected
component.
Cross Reference - Cross reference information is displayed for items
referenced within a protected component, but users are not allowed to
navigate to the location within the protected component.
Double-clicking to navigate to a protected component beeps and
displays a message on the status bar indicating that users are unable to
edit the component and that the source is not available.
The Go to Location menu item is unavailable.
Go To - There is no edit item in the Go To dialog box for a protected
component.
Cut, Copy, Paste - Users can copy, paste, and drag and drop protected
components from the Controller and Logical Organizers.
IMPORTANT
Use caution when copying and pasting components between different versions
of the Logix Designer application. The application only supports pasting to the
same version or newer version of the application. Pasting to an earlier version
of the application is not supported. When pasting to an earlier version, the
paste action may succeed, but the results may not be as intended. You cannot
paste protected components from later versions of the application into earlier
versions of the application. For example, attempting to paste from version 19
into version 18 or from version 20 into version 19 will fail.
In version 18 and earlier of RSLogix 5000 software, only IEC-61131 compliant
source keys are recognized. Each source key must begin with a lowercase
character a-z or underscore character ( _ ), and contain only characters
lowercase a-z, 0-9, and an underscore character ( _ ). You can enter uppercase
A-Z characters in RSLogix 5000 software or in the source key file, but the
uppercase characters are converted to lowercase. Source keys are limited to 40
characters in length.
In version 19 and later of the application, source keys are case-sensitive and
may contain any printable ASCII character, excluding the space character.
This includes uppercase A-Z, lowercase a-z, numbers 0-9, and symbols such as
"!@#$%. Source keys are limited to 40 characters in length.
Version 19 and later of the Logix Designer application supports associating
names with source keys. Source key names are descriptive text that help
identify source keys. Where appropriate, the Logix Designer application will
display the source key name in place of the source key itself to provide an
additional layer of security for the source key.
Use descriptive names to help identify the purpose of the source. For instance,
a source key used to secure components that field engineers require access
might be named, Field Engineer.
About source keys
Source key names
Chapter 2 Configuring source protection in the Logix Designer application
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 21
IMPORTANT
If the same source keys will be used with version 18 and earlier and version 19 and later
of the Logix Designer application, begin each source key with a lowercase character
a-z, or an underscore character ( _ ), and use only characters lowercase a-z, 0-9 , or an
underscore character ( _ ) within the source keys.
If you use source key names in version 19 and later of the application, and your source
keys are IEC61131-3 compliant, your source keys will still work in version 18 and earlier.
Source keys that are available to the application through an sk.dat file are
unencrypted. We recommend that you write down your source keys or back
up and store the sk.dat file in a secure location. If necessary, the individual
keys can be distributed or provided to the necessary parties.
IMPORTANT
Source key files are created in an ANSI format in Logix Designer versions 18 and earlier.
In versions 19 and later, the Logix Designer application creates UTF-8 formatted sk.dat
files, and modified ANSI sk.dat files are converted to UTF-8 sk.dat files.
Source keys must not appear on the first line of a UTF-8 formatted sk.dat file. The first
line of UTF-8 formatted sk.dat files is ignored in Logix Designer versions 18 and earlier.
Versions 19 and later insert a header on the first line of the sk.dat file if one is not
already present.
Follow these steps to assign a name to an existing source key.
1. Select Tools > Security > Configure Source Protection.
2. In the Source Protection Configuration dialog box, select Source Key
Configuration.
3. In the Source Key Configuration dialog box, select View to open the
sk.dat file with a text editor, such as Notepad.
4. Select at the end of an existing, unnamed source key, and press Enter.
Source keys are case sensitive and may use special characters, such as
@#$%(){}[].
5. Press Tab, and type a name for the source key.
Source key file
Chapter 2 Configuring source protection in the Logix Designer application
22 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
Tip: Source keys always begin in the first column of the line in the text editor. A source key
name must be on the line immediately following the source key that it is associated with,
preceded on the line by at least one space. Subsequent lines after the source key that are
preceded with spaces are ignored by the application, and can be used for comments.
6. Save the file. If you used an editor other than Notepad, make sure you
save the file as a text file.
7. Close the Source Key Configuration dialog box and the Source
Protection Configuration dialog box.
8. Select Tools > Security > Configure Source Protection to re-open the
Source Protection Configuration dialog box. The source key name that
you added to the sk.dat file appears as the source key name.
Follow this procedure to apply Source Key protection to a project component.
IMPORTANT
Source Protection can be applied only on a project file that is offline.
Tip: For Add-on Instructions, Source Protection settings cannot be modified if the Add-On Instruction
is sealed. If you wish to source protect and seal an Add-On Instruction, you must apply the source
protection settings before sealing.
To apply source key protection to a component
1. Open an offline project file in the Logix Designer application.
2. On the menu bar, select Tools > Security > Configure Source
Protection.
3. In the Source Protection Configuration dialog box, select one or more
components that require protection, and select Protect.
Apply Source Key
protection to a component
Chapter 2 Configuring source protection in the Logix Designer application
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 23
By default, the dialog box shows the Protection view in which
components are organized based on the protection applied to them.
When you select the Container view, the components are organized
based on the folder structure in the Controller Organizer and the
Logical Organizer.
4. In the Protect dialog box, on the Protection Type list, select Source
Key.
5. In the Source Key to Apply Selected Components list, select the
individual source key for the component.
Chapter 2 Configuring source protection in the Logix Designer application
24 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
6. If appropriate, retype the new key in Confirm New Source Key. To
display the source keys in a readable format, select the Show Source
Key check box.
7. If you want to apply a source key name, type the name in Source Key
Name. Do not exceed 40 characters.
8. To allow users to view the logic and local tags on a system that does not
have the source key required for access, select the Allow viewing of
component(s) check box.
9. After you enter the applicable information, select OK.
10. (optional) In the Source Protection Configuration dialog box, select
Source Key Configuration to open the Source Key Configuration
dialog box and complete details about the source key file location:
Select Specify to change the path to the source key file location.
Select View to view the source key file.
Select Clear to remove the location of the source key file (sk.dat).
You are then given the option to delete the source key file.
Select Disable Configuration to remove the menu item that invokes
the Source Protection Configuration dialog box. You can then clear
the file location, which is the path listed under Source Key Provider,
or delete the source key file.
11. Close the Source Protection Configuration dialog box and save the
project file.
Follow these steps to configure a source key file location.
Specify a source key file and location
1. Open an offline project file in the Logix Designer application.
2. On the menu bar, select Tools > Security > Configure Source
Protection.
Tip: This option is not available until you run RS5KSrcPtc.exe on your workstation. See
Enabling source protection on page 18.
Specify a Source Key file
and location
Chapter 2 Configuring source protection in the Logix Designer application
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 25
3. In the Logix Designer dialog box, select Yes to specify a file location.
Source protection requires that you specify a source key file location on
your workstation.
4. In the Specify Source Key File Location dialog box, select Browse .
5. In the Browse for Folder dialog box, select the folder to store the key
file, and select OK.
You can save the key file in any accessible folder. In this example the
path to the key file folder is C:\RSLogix 5000\Projects folder.
6. In the Specify Source Key File Location dialog box, select OK.
The location you selected appears in the Source Protection
Configuration dialog box under Source Key Provider.
If the application does not find a key file in the specified location, the
application prompts you to create a new key file.
Tip: To check for a specific location, on the Source Protection Configuration dialog box,
select
Specify
. A window appears with the location if one exists on your workstation.
7. Select Yes to create a new key file.
Chapter 2 Configuring source protection in the Logix Designer application
26 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
Follow these steps to allow source-protected components to be viewed in a
read-only format on a system that does not have the source keys.
To view components without a key
1. On the menu bar, select Tools > Security > Configure Source
Protection.
2. In the Source Protection Configuration dialog box, select one or more
components that require protection and select Protect.
3. Apply a source key to the component.
4. Select the Allow viewing of components check box, and select OK. In
the Source Protection Configuration dialog box, +View appears for
components that are viewable on workstations that do not have the
source key.
5. Select Close.
6. Save the project file and download it to the controller.
Users can open the routine as read-only on a system that does not
contain the source key for the routine, but cannot modify the routine.
Routines or Add-On Instructions that are protected, but are not
configured as viewable, cannot be opened.
Tip: Source-protected content cannot be copied from Logix Designer versions 19 and later
and pasted into earlier software versions. The pasting function is disabled in previous
software versions when source-protected content is placed on the clipboard.
View components without a
key
Chapter 2 Configuring source protection in the Logix Designer application
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 27
After you apply source key protection to a component, you can verify that the
source key protection is working. To verify a component is protected,
temporarily disable the source key on your workstation.
Follow these steps to verify source key protection by specifying the path to an
empty sk.dat file.
1. On the Source Protection Configuration dialog box, select Specify.
2. On the Specify Source Key File Location dialog box, select a directory
that does not contain an sk.dat file. For example, C:\RSLogix
5000\Projects\Empty.
3. When a message appears asking if you want to create a new file, select
Yes.
4. When the message appears asking if you want to create a new
directory, select Yes. The software points to an empty sk.dat file, which
mimics a user who does not have a source key.
5. Verify that you cannot access the protected component.
6. On the Specify Source Key File Location dialog box, switch back to the
directory that contains your original sk.dat file.
You can delete a source key file (sk.dat) from a workstation.
IMPORTANT
Write down the source keys or make a copy of the sk.dat file and store it in a secure
location before deleting the sk.dat file.
To remove access to a protected routine
1. Open the protected project.
2. Select Tools > Security > Configure Source Protection to open the
Source Protection Configuration dialog box.
3. Select Source Key Configuration.
4. On the Source Key Configuration dialog box, select Clear.
5. When a dialog box asks for confirmation that you want to delete the
source key file, select Yes to remove the source key file from the
workstation.
License Source Protection limits access to projects to only users with the
required license. Users without the required license cannot open the project
or import components protected by the license. A CmStick containing the
corresponding license must be plugged into a USB port on the computer to
open the project containing the component.
License protection uses licenses that you create and administer through a
license portal. Refer to your license portal help for details on using the portal.
Verify source key
protection on a component
Remove access to a
protected routine
License Source Protection
for components
Chapter 2 Configuring source protection in the Logix Designer application
28 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
Tip: License Source Protection is not supported on the following routine types on Compact
GuardLogix 5380, CompactLogix 5380, CompactLogix 5480, ControlLogix 5580, and GuardLogix 5580
controllers:
Sequential Function Chart routines.
Function Block Diagrams, unless the Function Block Diagram is included in an Add-On Instruction.
When using License Protection on CompactLogix 5380, CompactLogix 5480,
and ControlLogix 5580 controllers, you can also apply Execution Protection
for the component, which allows execution of the component only on a
specific controller family, or only on controllers in a specific controller family
that contain the execution license.
The table lists the permissions provided by licenses.
Permission
Description
Use This is the minimum permission available for a license. Allows a user to
open, import, upload, or download the project.
Important:
A CmStick containing a license with Use permission must be
present locally on any USB port on the computer. Use permission cannot
be obtained from a network license server. All other license privileges can
be contained on the local CmStick, or provided by a license server on the
network.
Tip:
On Compact GuardLogix 5380, CompactLogix 5380, CompactLogix
5480, ControlLogix 5580, and GuardLogix 5580 controllers, a Use license is
not required to open, import, upload, or download a project containing a
License-Protected component when that component has been locked.
View Allows users to view routine logic for the component, or local tags for an
Add-On Instruction. It also enables printing, searching, and cross
referencing. Editors and properties dialog boxes for the component are
limited to read-only, and changes are prevented.
Tip:
A View license is required to unlock, view, and re-lock a
License-Protected component.
Edit Allows users to edit the routine or Add-On Instruction.
Tip:
A View license is required to unlock, edit, and re-lock a
License-Protected component.
Copy
Allows users to copy the logic in the routine or Add-On Instruction.
Export Allows users to export the routine or Add-On Instruction in a
non-encrypted format.
Protect Allows users to enable or remove license protection from a component.
Important:
A user can add or remove protection from a component only
when the Protect permission exists on the license currently protecting
that component.
License Source Protection on a component affects the following features:
Editing - If the license does not contain the View permission, the
Language editor does not open, the edit menus are unavailable in the
Controller Organizer and the Logical Organizer, and the component
icon is grayed out. With View permission, the editor opens in
read-only mode. If the license contains Edit permission, editing is
allowed.
Protect components with
Licenses
Chapter 2 Configuring source protection in the Logix Designer application
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 29
Printing - Routines cannot be printed unless the license contains View
permission. Add-On instructions can be printed, but the routines and
local tags are not printed without View permission.
Exporting - The protected component is written to the export file in an
encoded format unless the license contains Export permission. To
export in non-encrypted text, the license must contain the Export
permission, and when saving the export file, the user must deselect the
Encode Source Protected Content option. Locked components are
always exported encoded.
Tip: To export protected components in non-encrypted text, you also must uncheck the
Always Encode Protected Content on Export
check box on the
General
tab of the
Workstation Options dialog box.
Component Properties - All controls on the dialog boxes of the
components are read-only unless the license contains Edit permission.
Search and Replace - Find All is the only available search type. Find
Next, Replace All, and Replace Next skip the protected component.
When the protected component is skipped, a message appears on the
status bar indicating the source is not available. This message is also
logged to the search results tab for a Replace All search. Edit and View
permissions control users' ability to search and replace.
When the license does not contain the View permission, users cannot view the
logic of a protected routine, and the Find All search result items do not
navigate to the found locations. This affects the following features:
Navigation - Users cannot navigate to a protected component.
Verification - Users cannot navigate to an error in a protected
component.
Cross Reference - Cross reference information is displayed for items
referenced within a protected component, but users are not allowed to
navigate to the location within the protected component.
Double-clicking to navigate to a protected component displays a
message on the status bar indicating that users are unable to edit the
component and that the source is not available.
Tip: Find does not search locked components even when a View license is
present.
The Go to Location menu item is unavailable.
Go To - There is no edit item in the Go To dialog box for a protected
component.
Cut, Copy, Paste - Users can copy, paste, and drag and drop source
protected components from the Controller Organizer or Logical
Organizer. Users cannot copy, paste, or drag and drop logic contained
within the source protected component unless the license contains
Copy permission.
Chapter 2 Configuring source protection in the Logix Designer application
30 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
IMPORTANT
Use caution when copying and pasting components between different versions
of the Logix Designer application. The application only supports pasting to the
same version or newer version of the application. Pasting to an earlier version
of the application is not supported. When pasting to an earlier version, the
paste action may succeed, but the results may not be as intended. You cannot
paste protected components from later versions of the application into earlier
versions of the application. For example, attempting to paste from version 19
into version 18 or from version 20 into version 19 will fail.
Execution Protection is an extension of License-Based Source Protection. You
can apply Execution Protection to limit the execution of routines and Add-On
Instructions, including equipment phase state routines, to controllers that
contain a specific execution license.
When you apply Execution Protection to a component, you first apply
License-Based Source Protection. Therefore, a user applying Execution
Protection must have the same credentials that are required to apply
License-Based Source Protection:
A CmStick containing a license with Use permission must be present
locally on any USB port on the computer. Use permission cannot be
obtained from a network license server. All other license privileges can
be contained on the local CmStick, or provided by a license server on
the network.
A license containing the Protect permission, either on a local CmStick
or provided by a license server on the network. When components are
locked, unauthorized users cannot view or edit the component, but
authorized users can run the project without a CmStick.
The following credentials are required to run a component that is protected by
Execution Protection:
After a component is locked, the controller running the component
must be of the same controller family as the controller on which you
locked the component. For example, when you apply License-Based
Source Protection and Execution Protection to a component on a 5580
controller and lock the component, you can only execute that
component on another 5580 controller. A component that was
protected on a 5580 controller cannot be executed on a 5380 controller.
To execute the component on a controller from a different family, you
must unlock the component and re-lock it on the different family
controller.
The controller running the component must contain the following
licenses on a CmCard:
The required Execution license (if any)
A valid FactoryTalk Activation license for Execution Protection
Add Execution Protection to
License-protected
components
Chapter 2 Configuring source protection in the Logix Designer application
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 31
Follow these steps to apply License Protection to one or more components.
Tip: In this version of the Logix Designer application, License Source Protection does not support
these routine types:
Safety routines.
Sequential Function Chart routines.
Function Block Diagrams on Compact GuardLogix 5380, CompactLogix 5380, CompactLogix 5480,
ControlLogix 5580, and GuardLogix 5580 controllers, unless the Function Block Diagram is included
in an Add-On Instruction. However, License-protected Function Block Diagrams are supported are
supported in both routines and Add-On Instructions on CompactLogix 5370, ControlLogix 5570,
Compact GuardLogix 5370, and GuardLogix 5570 controllers.
Tip: Cannot modify the Source Protection settings if the Add-On Instruction is sealed. To source
protect and seal an Add-On Instruction, apply the source protection settings before sealing.
IMPORTANT
On CompactLogix 5380, CompactLogix 5480, ControlLogix 5580, Compact GuardLogix
5380, and GuardLogix 5580 controllers, to open a project when a component is
license-protected but not locked, insert a CmStick containing the corresponding
license into a USB port on the computer. A locked component does not require a
corresponding license to open the project or use the component.
To apply license protection to one or more components
1. Select Tools > Security > Configure Source Protection to open the
Source Protection Configuration dialog box.
2. Insert the CmStick containing the license that you want to use to
protect the component into the USB port on the computer. Note that
licenses must contain the Protect permission to be used to protect
components. If a license does not contain the Protect permission, it
will not appear in the list of licenses.
3. In the Source Protection Configuration dialog box, select the
component to be protected and select Protect.
Apply License Protection to
one or more components
Chapter 2 Configuring source protection in the Logix Designer application
32 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
4. In the Protect dialog box, select the license to apply.
5. On Compact GuardLogix 5380, CompactLogix 5380, CompactLogix
5480, ControlLogix 5580, and GuardLogix 5580 controllers, select the
Execution Protection type:
Protect with controller key only. This option is selected by default.
With this option selected, the component, when locked, runs only
on a controller in the same family as the one specified for the
project. For example, if you lock a License-Based Protected
component for a project on a 5580 controller, the component can
only be executed on another 5580 controller.
Protect with controller key and specific license. When you select
this option, the component runs only on a controller in the same
family as the one specified for the project and that contains a
CmCard with the execution license that you select.
If you select Protect with controller key and specific license, select
the execution license from the list of available licenses.
On CompactLogix 5380, CompactLogix 5480, ControlLogix 5580,
Compact GuardLogix 5380, and GuardLogix 5580 controllers, after
components are protected, they can also be locked. Locking a
Chapter 2 Configuring source protection in the Logix Designer application
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 33
component prevents users from viewing or editing the component but
allows authorized users to run it.
6. Select OK to return to the Source Protection Configuration dialog box.
Tip: To save changes to a component that is protected with License-Based Source
Protection, a CmStick containing the required license must be plugged into the computer
running the Logix Designer application.
Make sure you save your edits to the project or lock the protected components before
removing the CmStick containing the required license. If the license is not present, you could
lose your edits to the project.
7. Close the Source Protection Configuration dialog box and save the
project file.
After you apply License Source Protection to a routine or an Add-On
Instruction, you can lock it on Compact GuardLogix 5380, CompactLogix
5380, CompactLogix 5480, ControlLogix 5580, and GuardLogix 5580
controllers.
When locking a component, the routine's logic is compiled into executable
code and encrypted. The code is decrypted by the controller when it is ready
for execution. As a result, sharing project files containing locked components
with users without licenses to use the locked components is possible. Those
users can use unprotected parts of the project, upload and download the
project file, and copy and paste locked components into other project files.
However, if a component is protected using the Protect with controller key
and specific license option, executing the project requires an SD card with the
correct execution license.
Tip: To lock or unlock a component, the source license must be present on a CmStick plugged into
the computer running the Logix Designer application, and the license must contain the View
permission.
IMPORTANT
When locking a routine or an Add-On Instruction, the data included in tags is protected,
but not to the extent that the logic is protected. If your tags contain sensitive data,
Rockwell recommends putting that data in character string literals rather than in tags.
Literals are protected at the same level as the logic in locked routines and Add-On
Instructions.
To lock a component.
1. Apply License Source Protection to the component.
2. In the Source Protection Configuration dialog box, select the
protected component.
3. Select Lock.
4. To unlock the component, select it and select Unlock.
Lock a component
Chapter 2 Configuring source protection in the Logix Designer application
34 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
Tip: When a component is License-Protected, lock and unlock it by selecting it in the
Controller Organizer
, right-clicking, and selecting
Lock
or
Unlock
. Use the
Security
toolbar
to lock and unlock a component or to lock all License-Protected components at once.
When a routine or an Add-On Instruction is protected by License Source
Protection, it should be locked if it is shared outside a trust boundary, such as
being emailed over the internet or sent to an end customer. Projects that
contain unlocked components are in a less secure state than locked
components and should not be distributed.
To lock all license-protected components in a project at once, use the Lock All
button on the Security toolbar.
To lock all components in a project
1. Apply License Source Protection to the components that you need to
protect.
2. On the Security toolbar, select the Lock All button. This button is
disabled when there are no components to be locked.
You can also select, on the main menu, Tools > Security > Lock all
unlocked content.
Tip: If an error prevents a component from locking, an error message appears. The Logix
Designer application still locks other components that can be locked without error.
To monitor license status and verify the license is not expired or removed,
insert a License Validation (LV) instruction in a Ladder diagram. The LV
instruction checks that a non-expired license associated with a routine or an
Add-On Instruction is present in the controller. Insert additional logic in the
routine to act on the license status.
Adjust network settings to provide additional privileges to users on the
network or to use License Source Protection when using a remote desktop
connection.
When sharing license privileges with users on the network consider:
Configure the network to allow communication between the devices
that need to share license privileges. Set TCP and UDP ports 22350 to
open on the computer that provides privileges.
Enable the license to share for network use. Use the License Portal to
configure licenses and optionally enable them for network use.
The computers that receive permissions from the remote workstation
must install a CmStick that contains the same license with Use
permission. Plug the CmStick into a USB port locally on the
computers.
Lock all License-Protected
content
Add an LV instruction to
monitor license status
Share License privileges
with other users on your
network
Chapter 2 Configuring source protection in the Logix Designer application
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 35
You can share license privileges with other users and provide license
privileges to users of remote desktop.
Follow these steps to provide license privileges to users on your network.
1. To open the CodeMeter Control Centerapplication, on the computer
that is going to provide additional privileges, navigate to the
C:\Program Files (x86)\CodeMeter\Runtime\bin folder and run the
CodeMeter.exe file.
IMPORTANT
Your computer should have a CmStick installed that contains a license with all
the privileges that you want to share. The CmStick should be plugged into a USB
port on your computer.
2. Select WebAdmin to open the CodeMeter WebAdmin window in your
default web browser.
Provide License privileges
to other users
Chapter 2 Configuring source protection in the Logix Designer application
36 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
3. Select Configuration > Server, select Run network server, and select
Apply.
Chapter 2 Configuring source protection in the Logix Designer application
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 37
4. Select Configuration > Access Control and select Advanced.
5. Under Default action, select Deny and select Apply.
6. Under Access Control Mode, select Basic.
7. Select Add and enter the list of users (user names, IP addresses, user
groups, or subnets) who can access your shared license. Select Apply.
Chapter 2 Configuring source protection in the Logix Designer application
38 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
8. On the CodeMeter Control Center, navigate to the Process tab to stop
and restart CodeMeter.
9. On the computers that need to receive the shared license privileges,
open the CodeMeter Control Center application.
IMPORTANT
A CmStick containing a license with
Use
permission must be present locally on
any USB port on the computer that receives shared permissions.
Use
permission cannot be obtained from a shared license.
10. Click WebAdmin to open the CodeMeter WebAdmin window.
Chapter 2 Configuring source protection in the Logix Designer application
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 39
11. On the Configuration tab, in the server list, add the name or IP
address of the computer that you configured as a license server.
12. Restart CodeMeter.
Tip: When the
Server Search List
is blank in the
CodeMeter WebAdmin
tool, CodeMeter
searches all servers that it finds on your subnet. When a user has a license that is also on a
license server, the user's permissions might be upgraded to match the license on the server.
To prevent accidental granting of privileges and to prevent CodeMeter from searching
unnecessarily, add
127.0.0.1
(the localhost IP address) to the
Server Search List
.
Follow these steps to provide license privileges for remote desktop users on
your network.
To provide license privileges for remote desktop users
1. On the remote desktop client computer, open the CodeMeter Control
Center application. To open the application, navigate to the
C:\Program Files (x86)\CodeMeter\Runtime\bin folder, and run the
CodeMeter.exe file.
Provide license privileges
for remote desktop users
Chapter 2 Configuring source protection in the Logix Designer application
40 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
IMPORTANT
Your computer should have a CmStick installed that contains a license with all
the privileges that you want to use remotely. The CmStick should be plugged
into a USB port on your computer.
2. Select WebAdmin to open the CodeMeter WebAdmin window in your
default web browser.
Chapter 2 Configuring source protection in the Logix Designer application
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 41
3. Select Configuration > Server, select Run network server, and select
Apply.
Chapter 2 Configuring source protection in the Logix Designer application
42 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
4. Select Configuration > Access Control and select Advanced.
5. Under Default action, select Deny and select Apply.
6. Under Access Control Mode, select Basic.
7. Select Add and enter the list of users (user names, IP addresses, user
groups, or subnets) who can access your shared license. Select Apply.
Chapter 2 Configuring source protection in the Logix Designer application
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 43
8. On the CodeMeter Control Center, navigate to the Process tab to stop
and restart CodeMeter.
9. Log onto the remote computer with remote desktop.
10. On the remote computer, open the CodeMeter Control Center
application.
IMPORTANT
A CmStick containing a corresponding license with
Use
permission must be
present locally on any USB port on the remote desktop server.
Use
permission
cannot be obtained from a remote computer.
Chapter 2 Configuring source protection in the Logix Designer application
44 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
11. On the Configuration tab, in the server list, add the name or IP
address of the computer that contains the needed permissions.
12. Navigate to the Process tab on the CodeMeter Control Center to stop
and then restart CodeMeter.
Tip: When the
Server Search List
is blank in the
CodeMeter WebAdmin
tool, CodeMeter
searches all servers that it finds on your subnet. When a user has a license that is also on a
license server, the user's permissions might be upgraded to match the license on the server.
To prevent accidental granting of privileges and to prevent CodeMeter from searching
unnecessarily, add
127.0.0.1
(the localhost IP address) to the
Server Search List
.
Securing a ControlLogix controller with the Logix
CPU Security Tool
You can secure a controller with the Logix CPU Security Tool. The Logix CPU
Security Tool is automatically installed when you install Logix Designer
version 17, 18, or 19. The tool is installed under the Logix Designer menu bar
on the Tools menu.
Chapter 2 Configuring source protection in the Logix Designer application
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 45
IMPORTANT
The Logix CPU Security Tool is supported only in Logix Designer application versions 17,
18, and 19. It is not supported in versions 20 and later.
1. Select the Start button, then select All Programs, then select Rockwell
Software, then select RSLogix 5000, and then select Logix CPU
Security Tool.
2. In the Logix CPU Security dialog box, select the RSWho button to
specify a path to the controller.
Chapter 2 Configuring source protection in the Logix Designer application
46 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
3. Select the controller that you want to secure and select OK.
The Logix CPU Security Tool displays the current status of the
controller. Notice that the controller in the following image is currently
unsecured and there is no password set in the controller.
4. Select Change Password.
Chapter 2 Configuring source protection in the Logix Designer application
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 47
5. In the Change Password dialog box, in the New Password box type a
password, and then in the Confirm New Password box, retype the
password. Select OK.
The Password Status for the controller changes to indicate a Password
exists in the controller, but the controller is not secured yet.
6. Select Secure Controller.
7. In the Secure Controller dialog box, in the Password box, type the
password for the controller and then select Secure.
Chapter 2 Configuring source protection in the Logix Designer application
48 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
8. If the controller has nonvolatile memory installed, you can select the
Save to Nonvolatile Memory after controller is secured check box to
save the security state of the controller to nonvolatile memory. Refer to
the Logix Designer application help for additional information on
using nonvolatile memory.
The Controller Security Status for the controller changes to indicate
that it is secured.
When you try to access a controller that has been secured with the Logix 5000
CPU Security Tool and you do not have a local copy of the project file on your
computer, the application prompts you to select the proper file.
Accessing a secured
controller
Chapter 2 Configuring source protection in the Logix Designer application
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 49
To access a secured controller
1. On the menu bar, select Communications, and then select Who Active.
2. In the Who Active dialog box, select the secured controller and select
Go Online.
Chapter 2 Configuring source protection in the Logix Designer application
50 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
If you do not have a local copy of the project file on your computer, the
application prompts you to select a file.
3. Select Select file to find the project file.
4. In the Enter New or Select Existing File dialog box, select the project
file and then select Select.
5. Select Yes to create and upload the project.
Chapter 2 Configuring source protection in the Logix Designer application
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 51
An unspecified communications dialog box appears indicating that the
application is now offline.
6. Select OK to continue.
If the project file already exists on your system, an error message
appears that indicates that the controller is secured and you cannot go
online.
To remove security from a controller
1. Start the Logix CPU Security Tool. Select the Start button, then select
All Programs, then select Rockwell Software, and then select Logix
CPU Security Tool.
2. In the Logix CPU Security dialog box, select the RSWho button to
specify a path to the controller.
Removing security from a
controller with the CPU
Security Tool
Chapter 2 Configuring source protection in the Logix Designer application
52 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
3. In the Browse for controllers to Secure/Unsecure dialog box, select the
controller that you want to be unsecured and then select OK.
4. In the Logix CPU Security -
project_name
dialog box, select Unsecure
Controller.
5. In the Unsecure Controller dialog box, in the Password box, type the
password for the controller and then select Unsecure.
Chapter 2 Configuring source protection in the Logix Designer application
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 53
The controller is now unsecured, but the controller still recognizes the
password.
6. Select Exit.
7. Select Yes. A message appears.
Select Yes to save the change. You can now go online with the
controller.
Follow these steps to remove a password.
1. In the Logix CPU Security - DayOfWeek dialog box, select Change
Password.
Removing a password
Chapter 2 Configuring source protection in the Logix Designer application
54 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
2. In the Change Password dialog box, remove the '****' empty string
and select OK.
The controller status is now UNSECURED.
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 55
Appendix A
Product policies and securable actions
supported by FactoryTalk Security
When used with the Logix Designer application, FactoryTalk Security
supports Product Policies and Securable Actions. You configure these
FactoryTalk Security settings in the FactoryTalk Administration Console.
Product Policies are not tied to a specific project, and may include the
following.
Securing the controller
Creating a new project (either through the New Controller dialog box,
or through the Translator Tool utility)
Updating your firmware
Securable Actions let you perform specific tasks on a specific project or group
of projects, and may include the following.
Viewing a project
Going online
Creating tags
Creating modules
In a safety controller project, you can specify additional protection to safety
components. For example, to create a safety program, you need to have access
granted for both of the following securable actions.
Safety: Modify Component
Program: Create
Keep the following considerations in mind when configuring security settings
for the Logix Designer application.
Security settings are obtained from the FactoryTalk Network
Directory.
FactoryTalk Security Emulator is not used by the Logix Designer
application, but may be required by other software.
FactoryTalk Local directory is not supported.
FactoryTalk Services Platform version 2.50 (SR5) or later supports associating
the project with a specific FactoryTalk Directory.
Appendix A Product policies and securable actions supported by FactoryTalk Security
56 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
Product Policies and Securable Actions
The Product Policies and Securable Actions listed here are configured in the
Network Directory using the FactoryTalk Administration Console. For details
see the FactoryTalk Security System Configuration Guide. That document is
available in the Rockwell Automation Literature Library. Click the following
link to open the Literature Library in a browser window:
Rockwell Automation Literature Library
This table lists FactoryTalk Security Product Policies.
Grant access to these actions
To allow a user to
Controller: Secure
Secure a project or controller.
Firmware: Update Update controller firmware.
Tip:
If the project is secured, the Securable Action
(Firmware:Update) is also required to perform firmware updates.
Firmware updates can be initiated within the Logix Designer
application WhoActive dialog box if a project is open but not
when the controller is online.
Print: Modify Options Modify print options.
Project: New
Create a new project, import a project or translate PLC-5/SLC.
Toolbar: Configure
Move, resize, hide or show toolbars.
Workstation: Modify Options
Modify workstation options.
This table lists FactoryTalk Security Securable Actions.
Tip: When you restrict access to specific project properties, such as tags or alarms, users might still
be able to adjust those properties or values using logic. To provide more complete protection for
project properties, consider restricting access to Routine: Modify Logic.
Grant access to these actions
To allow a user to
Add-On Instruction: Create Create an Add-On Instruction.
Add-On Instruction: Delete
Delete an Add-On Instruction.
Add-On lnstruction: Export
Export an Add-On Instruction.
Add-On lnstruction: Export Unencoded Export an Add-On Instruction in clear text.
Tip:
Users must also be granted the
Add-On Instruction: Export
permission to export
an AOI, or granted the
Project: Export
permission to export the entire project.
Tip:
To export in clear text, you must clear the
Encode Protected Content
checkbox
on the Export dialog box. You must also have the required source key or license if the
component is protected with Source Protection.
Add-On Instruction: Modify Edit Add-On Instruction properties, tags, logic or whether a user can configure source
protection.
Add-On Instruction: View Logic
View the internal information in an Add-On Instruction.
Alarm Definition: Create Create new alarm definitions.
An alarm definition is associated with an Add-On Instruction (AOI) or a defined data
type. When a tag is created using a data type or an AOI that has alarm definitions,
alarms are created automatically based on the alarm definitions.
Product policies and
securable actions
Appendix A Product policies and securable actions supported by FactoryTalk Security
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 57
Grant access to these actions
To allow a user to
Alarm Definition: Delete
Delete alarm definitions.
When a user who is granted the
Alarm Definition: Delete
permission deletes an alarm
definition for a data type or an Add-On Instruction (AOI), the corresponding alarms
based on the alarm definition are deleted, even if the user has not been granted the
Alarm: Delete
permission.
When a user deletes a data type or an AOI, all alarm definitions associated with that
data type or AOI are deleted, even if the user has not been granted the
Alarm
Definition: Delete
permission.
Alarm Definition: Modify Properties Modify the properties of a tag-based alarm.
When a user who is denied the
Alarm Definition: Modify Properties
permission
imports a project or a project component that requires changes to existing tag-based
alarm definitions, the import fails.
Alarm Definition: Modify Required Use Modify Required to be used and evaluated for all alarm instances.
When a user is denied this permission, the user will be unable to modify the
Required
to be used and evaluated for all alarm instances
in the Logix Designer application
and Logix Services.
Alarm: Clear Alarm Log
Clear the contents of the alarm log from the controller.
Alarm: Configure Direct Commands Respond to a tag-based alarm using the
Acknowledge
,
Shelve
,
Disable
, and
Reset
buttons on the Alarm Properties dialog box - Status tab.
Alarm: Create Create new tag-based alarms.
When a user who is denied the
Alarm: Create
permission imports a project or a
project component that requires new alarms to complete the import, those alarms are
created.
Alarm: Delete Delete tag-based alarms.
When a user who is granted the
Tag: Delete
permission deletes a tag that has alarms
associated with it, those alarms are deleted.
Alarm: Modify Properties Modify the properties of a tag-based alarm.
Tip:
When a user who is denied the
Alarm: Modify Properties
permission imports a
project or a project component that requires changes to existing tag-based alarms,
the import fails.
Alarm: Modify Use Modify Use and evaluate alarm.
Marks all alarm instances as active and ready for evaluation. This check box is cleared
by default.
Enable or disable a tag-based alarm using the
Use and evaluate alarm
check box on
the Alarm Properties dialog box - Advanced tab.
Component: Modify Permission Set
Change which permission set is associated with a component.
Controller: Clear Faults Edit the fault log, including clearing faults.
Controller: Lock/Unlock
Lock or unlock the controller for online edits.
Controller: Modify Mode
Change controller modes.
Controller: Modify Properties
Edit controller properties.
Controller: Modify Revision
Convert the .acd file to a higher revision.
Controller: Modify Type Change controller types.
If a user is granted
Controller: Modify Revision
privilege, but is denied
Controller:
Modify Type
, in most situations the user will be unable to change the type of
controller.
Controller: Unsecure
Unsecure a secured controller.
Data Log: Create
Create a data log.
Data Log: Modify
Modify a data log.
Data Log: Delete
Delete a data log.
Data Log: Enable/Disable
Enable or disable data logging.
Data Log: Read Log Data Value Read a data log value.
Appendix A Product policies and securable actions supported by FactoryTalk Security
58 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
Grant access to these actions
To allow a user to
Data Log: Clear Log Data Value
Clear a data log value.
Firmware: Update
Use the Logix Designer application to update controller firmware.
The Product Policy (Firmware:Update) is also required to perform firmware updates.
Firmware updates can be initiated within the Logix Designer application
WhoActive
dialog box if a project is open, but not when the controller is online.
Language: Modify Properties Associate project documentation with a language, set default language, add or delete
a language.
Language: Switch Language
Select a different language for product documentation.
Module: Create Create modules in the Controller Organizer.
If
Module: Create
is denied, the
New module
and
Paste
options are not enabled on
the I/O tree menu. The
Import Module
option is enabled.
A message displays that states that
Module: Create
must be granted. Selecting
OK
to import a module is not successful, and the dialog box closes.
If the
Select Module Type
dialog box is open and
Module: Create
is denied, the
Create
option is enabled unless you select a different module in the dialog box.
If you select
Create
, the create wizard launches.
If the create wizard is open and
Module: Create
is denied, you can perform all the
steps to configure the module. When the you select
OK
to create the module, you
receive the error Module: Create needs to be granted.
Module: Create and Safety: Modify
Component
Create safety I/O configuration.
Denying
Safety: Module Component
does not affect the ability to create a safety
module.
If
Module: Create
is granted, but
Safety: Module Component
is denied, you can
create safety modules.
Module: Delete Delete modules in the Controller Organizer.
If
Module: Delete
is denied, the
Cut
and
Delete
options are not enabled on the I/O
tree menu.
If you select the
Cut
or
Delete
option, you receive a confirmation message, then a
Module: Delete
is denied message. When you select
OK
, your receive the error
Module: Delete
needs to be granted.
Module: Delete and Safety: Modify
Component
Delete safety I/O configuration.
Denying
Safety: Module Component
does not affect the ability to delete a safety
module, or a sub-tree that contains safety modules.
If
Module: Delete
is granted, but
Safety: Module Component
is denied, you can
delete a safety module, or a sub-tree that contains safety modules.
Module: Maintenance High
Perform high impact operations such as module reset and calibration.
Module: Maintenance Low Perform low impact operations such as resetting electronic fuses.
Module: Modify Properties Edit module properties.
If
Module: Module Properties
is denied, edit the configuration in the profile, including
the Module Definition in an Add-On Profile.
When you select
OK
or
Apply
, you receive the error
Module: Modify Properties
needs
to be granted.
Appendix A Product policies and securable actions supported by FactoryTalk Security
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 59
Grant access to these actions
To allow a user to
Module: Modify Properties and Safety:
Modify Component
Modify safety I/O configuration.
Safety: Module Component
affects only safety-related areas of profiles.
If
Safety: Module Component
is denied, the
Safety Network Number
dialog box on
the
General
page of either a Classic or Add-On Profile cannot be opened.
If the
Safety Network Number
dialog box is already open when
Safety: Module
Component
is changed from granted to denied, then you can complete the
operation to change the
Safety Network Number
and successfully apply the
updates.
If
Safety: Module Component
is denied, all controls that modify safety-related
configuration are disabled when you select a different page, or select a different
menu option. Some controls such as the
Safety Input RPI
on the
Safety
page,
remain enabled, but only if the
Safety
page is current when
Safety: Module
Component
changed from granted to denied.
If
Safety: Module Component
is denied, the
Advanced Connection Reaction Time
Limit Configuration
dialog box on the
Safety
page cannot be open.
If the
Advanced Connection Reaction Time Limit Configuration
is already open
when
Safety: Module Component
is changed from granted to denied, then you can
complete the operation to change and accept the updates and they are successfully
applied.
If there are pending edits to any safety-related control when
Safety: Module
Component
is changed from granted to denied, then you can accept the updates
and they are successfully applied.
Module: View Properties View module properties.
Users with this permission can open device profiles and, when online with the
controller, use the profile to directly interact with modules and carry out actions such
as changing IP addresses.
When this permission is denied, users cannot open device profiles.
Motion: Command Axis Perform axis direct commands.
Motion: Modify Configuration
Modify axis, coordinate system, or motion group properties.
Nonvolatile Memory: Load Load from non-volatile memory.
Nonvolatile Memory: Store
Store to non-volatile memory.
Phase: Create
Create equipment phases.
Phase: Delete
Delete equipment phases.
Phase: Manual Control
Manually control equipment phases.
Phase: Modify Properties Edit equipment phases.
PLC/SLC: Modify Tag Mappings
Map PLC or SLC messages.
Plug-In: Display
Display plug-ins.
Print: Report Print reports.
Program: Create
Create programs.
Program: Create and Safety: Modify
Component
Create a safety program.
Program: Delete
Delete programs.
Program: Delete and Safety: Modify
Component
Delete a safety program.
Program: Modify Properties Edit program properties.
Program: Modify Properties and Safety:
Modify Component
1
Modify properties of a safety program.
Program: Modify Properties and Safety:
Modify Component
Change class property of a standard program to safety.
Project: Compact Compact a project file.
Project: Download Download a project to a controller.
Appendix A Product policies and securable actions supported by FactoryTalk Security
60 Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
Grant access to these actions
To allow a user to
Project: Export
Save a project in .L5K or .L5X format.
Project: Go Online
Go online with a project.
Project: Modify Path Set, clear, or modify the controller path associated with a given project.
Project: Open Open a (read-only) version of the project.
If users do not have the ability to open and view the project, they do not have the
ability to do anything else with it.
Project: Save
Save a project.
Project: Save As Save a project to a new .acd file.
Project: Upload
Upload a project from a controller.
Routine: Create
Create a routine.
Routine: Create and Safety: Modify
Component
Create a safety routine.
Routine: Delete
Delete a routine.
Routine: Delete and Safety: Modify
Component
Delete a safety routine.
Routine: Export
Export a routine.
Routine: Export Unencoded
Export a routine in clear text.
Routine: Manual Control
Manually control routine logic.
Routine: Modify Logic
Edit routine logic.
Tip:
When you restrict access to specific project properties, users might still be able
to adjust those properties or values using logic. To provide more complete protection
for project properties, consider restricting access to Routine: Modify Logic.
Routine: Modify Logic and Safety: Modify
Component
Edit safety routine logic.
Routine: Modify Properties
Edit routine properties, configure routine source protection.
Routine: Modify Properties and Safety:
Modify Component
Edit safety routine properties.
Routine: View Logic
View the logic in a routine.
Safety: Generate/Delete Signature
Generate or delete a Safety Signature.
Safety: Lock/Unlock Lock or unlock edits on safety application.
Safety: Lock/Unlock Modify safety lock or unlock passwords.
Safety: Modify Component
Create, delete, or modify safety components.
Tip:
The standard component privileges are required in addition to this privilege. For
example, to create safety tags, the
Tag: Create
privilege is required in addition to the
Safety: Modify Components
privilege.
If
Module: Create
is denied, the
New module
and
Paste
options are not enabled on
the I/O tree menu. The
Import Module
option is enabled.
A message displays that states that
Module: Create
must be granted. Selecting
OK
to import a module is not successful, and the dialog box closes.
If the
Select Module Type
dialog box is open and
Module: Create
is denied, the
Create
option is enabled unless you select a different module in the dialog box.
If you select
Create
, the create wizard launches.
If the create wizard is open and
Module: Create
is denied, you can perform all the
steps to configure the module. When the you select
OK
to create the module, you
receive the error
Module: Create
needs to be granted.
Safety: Modify Properties
Modify the controller's safety configuration.
Safety: Modify Tag Mappings
Create safety tag mapping.
Safety: Modify Tag Mappings
Delete safety tag mapping.
Safety: Modify Tag Mappings
Modify safety tags mapped to standard tags.
Sequence: Create Create an equipment sequence.
Sequence: Delete Delete an equipment sequence.
Appendix A Product policies and securable actions supported by FactoryTalk Security
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 61
Grant access to these actions
To allow a user to
Sequence: Manual Control
Take manual control of an equipment sequence.
Sequence: Modify Properties
Modify the properties of an equipment sequence.
Tag: Create Create tags.
Tag: Create and Safety: Modify Component
Create a safety tag.
Tag: Delete
Delete tags.
Tag: Delete and Safety: Modify Component
Delete a safety tag.
Tag: Delete, Safety: Modify Tag Mappings,
and Safety: Modify
Delete standard tag that is mapped to a safety tag.
Tag: Force
Force tags and enable or disable existing forces.
Tag: Force and Safety: Modify Component Force safety tags.
Tag: Modify Constant Property
Change Constant property of a tag.
Tag: Modify Constant Tag Values Change values of a Constant Tag.
Tag: Modify Properties Edit tag properties.
Tag: Modify Properties and Safety: Modify
Component
Edit safety tag properties.
Tag: Modify Properties and Safety: Modify
Component
Change class property of a standard tag to safety.
Tag: Modify Properties and Safety: Modify
Tag Mappings
Modify safety or standard tag properties of a tag contained in a safety mapping.
Tag: Modify Values
Change tag values.
Tag: Modify Values and Safety: Modify
Component
Change safety tag values.
Task: Create
Create tasks.
Task: Delete
Delete tasks.
Task: Modify Properties
Edit task properties, including program scheduling.
Task: Modify Properties and Safety: Modify
Component
2
Modify safety task properties.
Trend: Create
Create trends.
Trend: Delete
Delete trends.
Trend: Modify Properties Modify trend properties.
Trend: Run Run trends.
User Defined Type: Create Create user-defined data types or string types.
User Defined Type: Delete
Delete user-defined data types or string types.
User Defined Type: Modify Edit user-defined data types or string types.
1
A safety program’s max scan time can be reset, regardless of the protection.
2
The safety task max scan time and max/min interval scan timers can be
reset, regardless of the protection.
Index
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023 63
Index
A
access
locked controller 48
Add-On Instructions
source protection 22
C
CodeMeter 34
controller
accessing locked files 48
remove security 51
D
delete
source key file 27
disable
source protection 18
F
FactoryTalk
security 11
file
sk.dat 20
source protection 22
I
install
source protection 18
L
License-based source protection 30
lock a License-protected component
33
LV instruction 34
P
password
removal 53
project
protect 15
source protect files 22
protect
project 15
R
remove
password 53
routine
source protection 22
S
security
FactoryTalk 11
sk.dat
file 20
source key
delete file 27
source protection
disable routine 18
install 18
types and overview 12
Allen-Bradley, expanding human possibility, Logix, Rockwell Automation, and Rockwell Software are trademarks of Rockwell Automation, Inc.
EtherNet/IP is a trademark of ODVA, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomayson Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenkÖy, İstanbul, Tel: +90 (216) 5698400 EEE YÖnetmeliğine Uygundur
Rockwell Automation Publication 1756-PM016S-EN-P - November 2023
Supersedes Publication 1756-PM016R-EN-P - November 2 022 Copyright © 2023 Rockwell Automation Technologies, Inc. All Rights Reserved. Printed in the U.S.A.
Rockwell Automation support
Use these resources to access support information.
Technical Support Center
Find help with how-to videos, FAQs, chat, user forums, and product notification
updates.
rok.auto/support
Knowledgebase
Access Knowledgebase articles.
rok.auto/knowledgebase
Local Technical Support Phone Numbers
Locate the telephone number for your country. rok.auto/phonesupport
Literature Library
Find installation instructions, manuals, brochures, and technical data publications.
rok.auto/literature
Product Compatibility and Download Center
(PCDC)
Get help determining how products interact, check features and capabilities, and
find associated firmware.
rok.auto/pcdc
Documentation feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at
rok.auto/docfeedback.